Smoke extract roof fanCF 63/6T HT FC6063T
Roof Smoke Extraction Fans
F400 · 120 min 0370-CPR-1551
F400: the fan runs in 400 °C smoke for 120 minutes per EN 12101-3, the European standard for smoke and heat exhaust fans.
| Model | CF 63/6T HT FC6063T |
|---|---|
| Series | CF / CF S / CF HT |
| Manufacturer | NOVOVENT |
| Airflow (max) | 12,097 m³/h |
| Diameter | 630 mm |
| Power | 1.1 kW |
| Current | 4.7 A |
| Noise | 62 dB(A) |
| Supply | MOTOR 6 POLOS · 6 POLE MOTOR · MOTEUR 6 PÔLES (1000 rpm) - ~III/5 |
| Fire rating | F400 (120 min) – EN 12101-3, outside risk area |
| Certificate | 0370-CPR-1551 |
Values per the official catalogue (maximum free-air). Not a substitute for duty-point selection.
About CF 63/6T HT FC6063T
CF 63/6T HT FC6063T is a CF / CF S / CF HT model in the Roof Smoke Extraction Fans category by NOVOVENT. It delivers up to 12,097 m³/h free-air airflow with a 630 mm diameter, a 1.1 kW motor at MOTOR 6 POLOS · 6 POLE MOTOR · MOTEUR 6 PÔLES (1000 rpm) - ~III/5, and a sound level of 62 dB(A). It is rated F400 for smoke and heat exhaust, certificate 0370-CPR-1551. Centrifugal roof fan for use outside the risk zone; motor isolated from extracted gases; weatherproof.
Similar models in this series
- CF 63/6T · 12,500 m³/h · 1.1 kW
- CF-S 63/6T · 12,500 m³/h · 1.1 kW
- CF 63/6T HT · 12,500 m³/h · 1.1 kW
- CF 56/4T · 11,278 m³/h · 2.2 kW
- CF-S 56/4T · 11,278 m³/h · 2.2 kW
- CF 56/6T · 8,016 m³/h · 0.55 kW